ODE R-FLEX Planning Details


Necessary Sheet Amount For Big Size Diameter Pipes (m2/m)

Steel Pipe
Diameterı
Exterior
Diameter
Insulation Thickness (mm)
Inch
mm
6 mm
9 mm
13 mm
19 mm
25 mm
32 mm
40 mm
50 mm
60 mm
4”
6
0,38
0,39
0,40
0,42
0,44
0,46
0,49
0,52
0,52
5”
8
0,46
0,47
0,48
0,50
0,52
0,54
0,57
0,60
0,60
6”
10
0,84
0,55
0,56
0,58
0,60
0,62
0,64
0,68
0,68
8”
12
0,71
0,72
0,73
0,75
0,77
0,79
0,82
0,85
0,85
10”
15
0,88
0,89
0,91
0,92
0,94
0,96
0,99
1,02
1,02
12”
18
1,04
1,05
1,06
1,08
1,10
1,12
1,15
1,18
1,18
14”
22
1,13
1,14
1,16
1,18
1,19
1,22
1,24
1,27
1,27

Optimum Insulation Thicknesses

Steel Pipe
Diameter
Interior
Diameter
Heating System
90/70°C
Cooling System
6/10°C
Warm line
60°C
Min. thickness to
stop condensation
Inch
mm
Insulation thickness (mm)
Efficiency
Insulation thickness (mm)
Insulation thickness (mm)
Insulation thickness (mm)
1/2”
22
13
%73
19
9
9
3/4”
28
13
%73
19
13
13
1”
35
13
%75
19
13
13
1 1/4”
42
13
%78
19
13
13
1 1/2”
48
19
%81
19
13
13
2”
60
19
%85
25
19
13
2 1/2”
76
19
%85
25
19
13
3”
89
19
%86
25
19
13
4”
114
25
%86
25
25
19
5”
139
25
%87
25
25
19
6”
165
32
%88
32
25
19
Acceptance
Criteria
Ambient Temp.:5°C
Fluid Temp. : 90°C
Ambient Temp.:5°C
Fluid Temp.: 90°C
Relative Hum.: %70
Ambient Temp.:5°C
Fluid Temp.:60°C
Ambient Temp.:35°C
Fluid Temp.:6°C
Fluid Temp.:%70

Terms of Use

Sarfiyat
ODE Konfix
250 - 400 gr/m2
Spread to both surfaces and applied after 10 min.
For Pipe :
Pipe length x insulation thickness x 1,3 x consumption
For Sheet :
Area to adhere x consumption amount
ODE R-FLEX Tapes
Pipe length is multiplied by 1,3
 
ODE PVC Tape
Pipe length is multiplied by 1,3
 

Sample Calculations with ODE R-FLEX ISOCALC Calculation Program

With the ODE R-FLEX Calculation Program:

 

For the Pipes calculations of:

  • Heat loss
  • Temperature decrease
  • Surface temperature
  • Minimum insulation thickness to prevent condensation
  • Freezing time

For smooth surfaces:

  • Calculations of heat loss can be done.


Sample Calculation of Minimum Insulation Thicknesses to Prevent Condensation According to Relative Humidity

 
Placement of Pipes Vertical
Temperature (°C) 25
Fluid temperature (°C) 5
Material ODE R-FLEX

Minimum Insulation Thicknesses to Prevent Condensation According to Relative Humidity for Two Different Pipe Diameters (22 mm and 114 mm)

Relative Humidity
(%)
Perspiration Temperatures
(%)
Insulation Thicknesses (mm)
Pipe Diameter (mm)
22
114
30
6,2
2,2
2,2
35
8,5
2,8
3,0
40
10,4
3,6
3,9
45
12,2
4,5
5,0
50
13,8
5,5
6,4
55
15,3
6,7
8,0
60
16,7
8,2
9,9
65
18,0
10,1
12,4
70
19,1
12,4
15,7
75
20,3
15,5
20,1
80
21,3
19,9
26,6
85
22,3
26,9
36,9
90
23,2
39,7
56,1
95
24,1
73,9
107,1