It is a closed-cell thermal insulation material manufactured from elastomeric rubber foam material in the form of sheets.
It is the insulation material of choice for air conditioning and cooling systems for its thermal insulation performance and high water vapor resistance. The product is ideal for insulating large diameter pipes, and ventilation ducts with rectangular or round cross sections. It is manufactured in various thicknesses and widths.
It can be produced in the range of 6-60 mm thickness.
ODE R-FLEX Sheet is manufactured in to three groups, DIAMOND , PRM (Premium) and STD (Standart), and with various types of facing.
PROPERTIES:
LAMINATED PRODUCTS:
ODE R-FLEX’s laminated products are;
R-FLEX ALUGLASS (Aluminum Glass Fabric)
R-FLEX AL-CLAD (Aluminium Cladding)
R-FLEX ALU (Aluminium Foil Facing)
R-FLEX METALIZED (Metalized Facing)
R-FLEX SA (Self Adhesive)
ODE R-FLEX DIAMOND/PRM/STD ALUGLASS Sheet
ODE R-FLEX DIAMOND/PRM/STD AL- CLAD Sheet
ODE R-FLEX DIAMOND/PRM/STD ALU Sheet
It is covered with aluminum facing with a thickness of 54 micron.
ODE R-FLEX DIAMOND/PRM/STD METALIZED Sheet
ODE R-FLEX DIAMOND/PRM/STD SA Sheet
Self-adhesive elastomeric rubber sheets.
SA with kraft paper
SA with HDPE film
Name of Product | λ (Thermal Conductivity) W/m.k | μ (Water Vapor Diffusion Resistance Factor) | Fire Class (EN 13501-1) |
R-FLEX DIAMOND Sheet | 0.032(-20ºC) | 11000 | B-s3-d0 |
0.034(0ºC) | |||
0.036(+20ºC) |
Name of Product | λ (Thermal Conductivity) W/m.k | μ (Water Vapor Diffusion Resistance Factor) | Fire Class (EN 13501-1) |
R-FLEX PRM Sheet | 0.032(-20ºC) | 7000 | B-s3-d0 |
0.034(0ºC) | |||
0.036(+20ºC) |
Name of Product | λ (Thermal Conductivity) W/m.k | μ (Water Vapor Diffusion Resistance Factor) | Fire Class (EN 13501-1) |
R-FLEX STD Sheet | 0.034(-20ºC) | 5000 | B-s3-d0 |
0.036(0ºC) | |||
0.038(+20ºC) |
Width | Thickness (mm) | |||||||||
6 | 9 | 10 | 13 | 19 | 25 | 32 | 40 | 50 | 60 | |
1000 | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ |
1200 | √ | √ | √ | √ | √ | √ | √ | √ | √ | - |
1500 | - | - | - | √ | √ | √ | √ | - | - | - |
ODE KONFiX (ODE R-FLEX ADHESIVE)
Synthetic rubber based super-strong adhesive used in ODE R-flex applications. Prevents convection currents at joints, facilitates easy and fast installation. Surfaces to which the product shall be applied should not be greasy or dusty, and ODE Konfix should be applied by using a roll, brush, or spray gun equally on both surfaces, and adhesion should be ensured under constant pressure. The drying period varies between 10 seconds and 4 minutes, and the time required for complete adhesion is 24 hours.
Adhesives | Quantity (kg) |
ODE KONFIX 14/1 | 14 |
ODE KONFIX 3/1 | 3 |
ODE EKO KONFIX 14/1 | 14 |
ODE EKO KONFIX 3/1 | 3 |
INSULATION OF AIR CONDITIONER DUCTS
1. Carefully clean the surface that is to be insulated. Nothing that can hinder adhesion should be left on the surface. Measure the duct surface that is to be insulated, and cut the appropriate size of ODE R-Flex Board from the roll. | ![]() |
2. Apply ODE R-FLEX Adhesive on the surface of the ODE R-FLEX that is to be attached to the duct and on the duct surface. To obtain good results, first cover the lower surface of the duct, then the side surfaces, and finally the top surface. | ![]() |
3. Attach the sides together using ODE R-FLEX Adhesive. | ![]() |
INSULATION OF TANKS
1. Carefully clean the entire surface before beginning insulation. Measure the height of the tank and its circumference with the ODE R-FLEX Board. | |
2. Transfer the measurements onto an ODE R-Flex Board and cut. Apply ODE R-Flex Adhesive to the entire surface of the ODE R-Flex Board using a spatula, and to the tank surface using a brush. Apply adhesive to the edges of the board and attach the board to the tank. Attach the sides together. | ![]() |
3. Measure against the ODE R-FLEX Board to insulate the convex area. | ![]() |
4. Calculate the diameter and draw the circle that will cover the convex area. Cut the circle out carefully at the marked places. | ![]() |
5. Apply ODE R-Flex Adhesive to the piece you have cut out and to the convex surface of the tank that is to be covered. | ![]() |
6. Place the piece on the area and press down to prevent it from sliding toward the outer edge. | ![]() |
7. When the piece has adhered to the tank surface, apply ODE R-Flex adhesive on the edges all along the circumference. After the adhesive is dry, attach the piece to the ODE R-FLEX Board covering the man body of the tank by firmly pressing the edges together. | ![]() |